| Application/type |
Outdoor sensor |
| Purpose |
Measure values |
| Sensor elements |
temperature, humidity |
| Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point |
| Interface |
Passive, Active, 0..5 V, 0..10 V, 4..20 mA, EnOcean (868 MHz), LoRaWAN® (868 MHz), RS485 Modbus, RS485 BACnet, Switch contact |
| On stock |
Yes |
| Configuration |
USEapp, App, uConfig, airConfig, BUS, jumper, DIP switches, LoRaWAN® Downlink, (depending on type) |
| Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 5 kΩ, min. load 10 kΩ |
| Output current |
2x 4..20 mA, max. load 500 Ω |
| Output switch contact |
2x floating contact NO for 24 V ~ or 24 V = / 3 A |
| Network technology |
RS485 Modbus, RS485 BACnet (MS/TP) |
| Radio technology |
EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW, standard radio telegram, EEP A5-02-14 (4BS), optionally configurable, LoRaWAN® (868 MHz) |
| Data transmission |
bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit), wake up time: 100 sec. (default), heartbeat cycle: every 10th wakeup, optionally configurable |
| Operating range temperature (°C) |
-20..+70 |
| Operating ranges temperature (°C) |
-30..+70 |
| Output signal temperature |
scaling analogue output, scaling according EEP, -20..+60 °C, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable |
| Operating range humidity |
max. 85% rH short term condensation |
| Accuracy temperature |
±0,3 K (typ. at 21 °C), ±0,4 K (typ. at 21 °C), ±1% of measuring range (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment, offset setting via app or uConfig |
| Measuring range humidity |
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, adjustable at the transducer, optionally configurable |
| Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C), ±5% between 30..70% rH (typ. at 21 °C) |
| Power supply |
15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV, solar cell, maintenance-free internal super cap, use of back-up battery possible for insufficiently lit environments, battery ER14505 (3,6 V), battery type AA (2x) |
| Power consumption |
typ. 0,4 W (24 V =), typ. 1 W (24 V =), max. 0,7 W (24 V =), max. 2,5 W (24 V =), 0,8 VA (24 V ~), 1,8 VA (24 V ~), 4,3 VA (24 V ~) |
| Material in touch with media |
Pipe, PC, pure white, length 53 mm, with filter stainless steel wire mesh |
| Display |
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
| Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white, transparent cover |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm² |
| Delivery content |
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories), incl. sun/rain protection PC, white |
| Packaging length (mm) |
100 |
| Packaging width (mm) |
128 |
| Packaging height (mm) |
65 |
| Packaging |
case packaging |
| Device length (mm) |
85 |
| Device width (mm) |
118 |
| Device height (mm) |
45 |
| Notes |
to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz), Please note our sheet 'Information EasySens® Radio', external antenna available on request |
| Gefahrgut |
No |