| Application/type |
Duct sensor, Immersion sensor |
| Purpose |
Measure values |
| Measured values |
temperature |
| Interface |
Passive |
| On stock |
Yes |
| Sensor |
NTC10k, Pt1000 DIN cl. B, Ni1000 DIN cl. B, Pt1000 1/3 DIN, Pt100 DIN cl. B, Ni1000TK5000, Pt100 1/3 DIN, NTC10k Precon, NTC10k Carel, NTC1,8k, NTC5k, NTC20k, LM235Z, DS18B20 1-wire, passive, SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
| Operating range temperature (°C) |
-80..+260 |
| Operating ranges temperature (°C) |
-50..+150, -50..+160, -80..+260 |
| Operating range temperature enclosure (°C) |
-30..+70 |
| Operating range humidity |
max. 85% rH short term condensation |
| Accuracy temperature |
±0,5 K (typ. at 21 °C), ±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend) |
| Material in touch with media |
Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media |
| Installation length (mm) |
50, 100, 150, 200, 250, 300, 450 |
| Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
| Connection cable |
2-wire, 3-wire, 4-wire |
| Mounting |
when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), or with enclosure USE-S with mounting clip, for use as immersion sensors please use immersion pocket THVADS / THMSDS |
| Delivery content |
incl. mounting clip enclosure USE-S pure white, incl. mounting set (screws and accessories) |
| Packaging |
case packaging |
| Gefahrgut |
No |