Application/type |
CO2 Traffic Light, Room sensor |
Purpose |
Measure values |
Measured values |
temperature, relative humidity, CO2 |
Operating elements |
4 favourite buttons |
Configuration |
NOVOSapp, uConfig |
Operating range temperature (°C) |
0..+50 |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,5 K (typ. at 21 °C) |
Measuring range humidity |
0..100% rH non-condensing |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 |
0..5000 ppm |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Power supply |
15..35 V = SELV, 19..29 V ~ SELV, mains adapter 100..230 V (50/60 Hz), max. 0,4A, Flush-mounted power supply 230 V (±10%, 50/60 Hz), max. 0.4 A |
Display |
TFT 3,5", 320x480 px, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure |
PC V0 |
Colour |
pure white |
Protection (IP) |
IP30, according to EN 60529 |
Connection |
tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting |
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Delivery content |
incl. stand and power supply unit |
Gefahrgut |
No |