Application/type |
Room sensor |
Purpose |
Measure values |
Measured values |
temperature, relative humidity, CO2, VOC |
Interface |
RS485 Modbus, RS485 BACnet, Passive, Active, 0..10 V |
Configuration |
Software/Plug-In for configuration, BUS, jumper, DIP switches, (depending on type) |
Sensor |
without sensor, Pt1000 DIN cl. B, Pt100 DIN cl. B, Pt1000 1/3 DIN, Pt100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC20k, NTC1,8k, NTC5k, LM235Z, passive, additional passive sensor, NDIR (non-dispersive, infrared) |
Output voltage |
0..10 V, 2x 0..10 V, 3x 0..10 V, 4x 0..10 V, min. load 5 kΩ, min. load 10 kΩ, heating + cooling or to control 6-way control valve |
Network technology |
RS485 Modbus, RS485 BACnet (MS/TP) |
Data transmission |
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) |
-35..+70 |
Operating ranges temperature (°C) |
0..+50, -35..+70 |
Output signal temperature |
0..+50 °C, scaling analogue output |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,5 K (typ. at 21 °C), ±1% of measuring range (typ. at 21 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend) |
Measuring range humidity |
0..100% rH non-condensing |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 |
0..2000 ppm |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) |
heated metal oxide semiconductor, self-calibration |
Power supply |
15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV |
Power consumption |
typ. 0,3 W (24 V =), typ. 0,4 W (24 V =), typ. 0,9 W (24 V =), max. 1,6 W (24 V =), 0,5 VA (24 V ~), 0,8 VA (24 V ~), 1 VA (24 V ~), 3,9 VA (24 V ~) |
Display |
3 LEDs for displaying air quality (traffic light function – TLF) |
Enclosure |
PC, central disc in design of the manufacturer, (varies depending on switch range), central disc Thermokon (frame selectable) |
Colour |
white, pure white brilliant, pure white matt, pure white matt, aluminium, Jung aluminium, black, studio white matt, studio white brilliant, alpin white, polar white matt, polar white brilliant |
Protection (IP) |
IP20, IP30, according to EN 60529 |
Connection |
terminal block, max. 1,5 mm², pluggable, cable entry via rear opening |
Switch ranges |
Berker, Busch-Jaeger, Feller, Gira, Jung, Merten, Peha, (please specify the desired frame when ordering) |
Switch range Berker |
S.1, B.3 aluminium, B.7, B.7 glass, Q.1, Q.3, K.5 aluminium/stainless steel |
Switch range Busch-Jaeger |
alpha nea®, Busch-axcent® with intermediate frame, Busch-balance® SI, Busch-Duro 2000® SI, future® linear with intermediate frame, impuls, Reflex SI, solo® with intermediate frame |
Switch range Feller |
EDIZIOdue, STANDARDdue |
Switch range Gira |
E2, E3, Esprit, Event, Flächenschalter with intermediate frame, Standard 55 |
Switch range Jung |
A 500, A 550, A creation, A plus, AS 500, CD 500 with intermediate frame, LS 990 with intermediate frame |
Switch range Merten |
1-M, Antik with intermediate frame, Artec with intermediate frame, Artec stainless steel with intermediate frame, Atelier-M, M-Plan, M-Pure, M-Smart |
Switch range Peha |
Aura, Aura glass |
Mounting |
flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm) |
Delivery content |
incl. frame |
Packaging length (mm) |
90 |
Packaging width (mm) |
90 |
Packaging |
case packaging |
Device length (mm) |
81 |
Device width (mm) |
81 |
Device height (mm) |
38 |
Gefahrgut |
No |