Thermokon
188.80 EUR
Item No.: 797818
Group: LRW2
Add to comparison list Add to project Show accessories

AKF10+

AKF10+ LRW 050.06

Duct sensor, Immersion sensor -50..+160 °C | LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V | IP65 according to EN 60529
Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media, 50 mm

Application/type Duct sensor, Immersion sensor
Purpose Measure values
Measured values temperature
Interface LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V
Configuration USEapp, uConfig, BUS, jumper, LoRaWAN® Downlink
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
Output voltage 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Radio technology LoRaWAN® (868 MHz)
Data transmission bidirectional
Operating range temperature (°C) -50..+160
Operating ranges temperature (°C) -50..+160
Output signal temperature scaling analogue output, 0..+160 °C (default setting), -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable
Operating range temperature enclosure (°C) -30..+70, -20..+70
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Power supply 15..35 V = SELV, 19..29 V ~ SELV
Power consumption max. 2,5 W (24 V =), 4,3 VA (24 V ~)
Material in touch with media Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media
Installation length (mm) 50
Enclosure USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Mounting when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), for use as immersion sensors please use immersion pocket THVADS / THMSDS
Delivery content incl. mounting flange MF6DS flexible, incl. mounting set (screws and accessories)
Packaging case packaging
Notes external antenna available on request
Option enclosure LCD 29x35 mm, RGB backlight
Gefahrgut No
188.80 EUR
Item No.: 797818
Group: LRW2
Add to comparison list Add to project Show accessories

Accessories

Top