DPA+
DPA7000+ VV MultiRange
Differential pressure transducer air or other non-flammable/non-aggressive gases, max. 40 kPa
differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig
0..+7000 Pa (default setting), 0..+1000 | 0..+1500 | 0..+2000 | 0..+2500 | 0..+3000 | 0..+4000 | 0..+5000 | 0..+7000 Pa, selectable at the device
Active, 0..5 V, 0..10 V | IP65 according to EN 60529
Application/type | Differential pressure transducer |
---|---|
Purpose | Measure values |
Measured values | differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig |
Interface | Active, 0..5 V, 0..10 V |
Configuration | USEapp, uConfig, jumper, DIP switches |
Sensor | MEMS membrane measuring element |
Output voltage | 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
Operating range temperature (°C) | -10..+50 |
Operating ranges temperature (°C) | -10..+50 |
Operating range humidity | max. 85% rH short term condensation |
Operating range pressure | air or other non-flammable/non-aggressive gases, max. 40 kPa |
Measuring range pressure | 0..+7000 Pa (default setting), 0..+1000 | 0..+1500 | 0..+2000 | 0..+2500 | 0..+3000 | 0..+4000 | 0..+5000 | 0..+7000 Pa, selectable at the device |
Accuracy pressure | ±10 Pa at range <2000 Pa, ±25 Pa at range >2000 Pa, deviation from calibration reference device (calibrator) |
Measuring range velocity | 0..750.000 m³/h, optionally configurable |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Enclosure | USE-L, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm², pressure connection male Ø=5,0 mm / Ø=6,3 mm, connection tube: PVC, soft |
Mounting | surface-mounted flat on base using screws, prepared for mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715 |
Delivery content | incl. mounting base enclosure USE-L pure white, incl. mounting set (screws and accessories), incl. pressure connection set and 2 m PVC connection hose |
Packaging length (mm) | 152 |
Packaging width (mm) | 128 |
Packaging height (mm) | 65 |
Packaging | case packaging |
Device length (mm) | 110 |
Device width (mm) | 105 |
Device height (mm) | 48 |
Notes | output protection circuit (reverse polarity protected) |
Gefahrgut | No |