FTK+
FTK+ 140 Basic RS485 Modbus
Duct sensor temperature, humidity
RS485 Modbus | IP65 according to EN 60529
Pipe, PA6, with filter stainless steel wire mesh, black, Ø=19,5 mm, 140 mm
| Application/type | Duct sensor |
|---|---|
| Purpose | Measure values |
| Sensor elements | temperature, humidity |
| Measured values | temperature, relative humidity |
| Interface | RS485 Modbus |
| On stock | No |
| Configuration | BUS, DIP switches |
| Network technology | RS485 Modbus |
| Operating range temperature (°C) | -20..+70 |
| Operating ranges temperature (°C) | -20..+70 |
| Operating range humidity | max. 85% rH short term condensation |
| Accuracy temperature | ±0,3 K (typ. at 21 °C), within default measuring range |
| Measuring range humidity | 0..100% rH non-condensing |
| Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
| Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
| Power consumption | max. 0,7 W (24 V =), 1,8 VA (24 V ~) |
| Material in touch with media | Pipe, PA6, with filter stainless steel wire mesh, black, Ø=19,5 mm |
| Installation length (mm) | 140 |
| Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour | pure white |
| Protection (IP) | IP65, according to EN 60529 |
| Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
| Delivery content | incl. mounting flange, incl. mounting set (screws and accessories) |
| Packaging length (mm) | 70 |
| Packaging width (mm) | 70 |
| Packaging height (mm) | 200 |
| Packaging | case packaging |
| Device length (mm) | 63 |
| Device width (mm) | 68 |
| Device height (mm) | 180 |
| Notes | air speed max. 12 m/s |
| Gefahrgut | No |