Contact Sensors
VFG54+ RS485 Modbus
Application/type | Contact sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | RS485 Modbus, Active, 0..5 V, 0..10 V |
Configuration | USEapp, uConfig, BUS, jumper, DIP switches |
Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Output voltage | 0..10 V or 0..5 V, live-zero configuration via app or uConfig, min. load 10 kΩ |
Network technology | RS485 Modbus |
Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | -35..+120 |
Operating ranges temperature (°C) | -35..+120 |
Output signal temperature | scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media | Sensor probe, brass, spring loaded sensor |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white, transparent cover |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm² |
Mounting | along the pipe or sideways |
Packaging | case packaging |
Accessories