LK+
LK+ CO2 temp LRW
Duct sensor temperature, CO2
LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V | IP65 according to EN 60529
Pipe, Ø=19,5 mm, black, length 150 mm, with filter stainless steel wire mesh
Application/type | Duct sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, CO2 |
Interface | LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V |
Configuration | USEapp, uConfig, jumper, LoRaWAN® Downlink |
Sensor | NDIR (non-dispersive, infrared) |
Output voltage | 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
Radio technology | LoRaWAN® (868 MHz) |
Data transmission | bidirectional |
Operating range temperature (°C) | 0..+50 |
Operating ranges temperature (°C) | 0..+50 |
Output signal temperature | scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,4 K (typ. at 21 °C), ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
Measuring range CO2 | 0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media | Pipe, Ø=19,5 mm, black, length 150 mm, with filter stainless steel wire mesh |
Installation length (mm) | 150 |
Enclosure | USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Delivery content | incl. mounting flange, incl. mounting set (screws and accessories) |
Packaging | case packaging |
Notes | air speed 0,3..12 m/s, external antenna available on request |