LP+
LP+ CO2 LCD temp VV L5000
Pendulum sensor, Room sensor temperature, CO2 | 0..+50 °C | Active, 0..5 V, 0..10 V – PVC, 0,25 mm², black, 5 m
| Application/type | Pendulum sensor, Room sensor |
|---|---|
| Purpose | Measure values |
| Sensor elements | temperature, CO2 |
| Measured values | temperature, CO2 |
| Interface | Active, 0..5 V, 0..10 V |
| On stock | No |
| Configuration | USEapp, uConfig, jumper |
| Sensor | integrated digital temperature transmitter, NDIR (non-dispersive, infrared) |
| Output voltage | 2x 0..10 V or 0..5 V, adjustable via jumper, min. load 10 kΩ |
| Operating range temperature (°C) | 0..+50 |
| Operating ranges temperature (°C) | 0..+50 |
| Operating range humidity | max. 85% rH short term condensation |
| Measuring range CO2 | 0..2000 ppm |
| Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
| Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
| Material in touch with media | Sensor head, black, length 126 mm |
| Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
| Enclosure | USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour | pure white |
| Protection (IP) | IP20, enclosure IP65, according to EN 60529 |
| Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
| Connection cable | PVC, 0,25 mm², black |
| Length connection wire (m) | 5 |
| Delivery content | incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
| Packaging length (mm) | 310 |
| Packaging width (mm) | 220 |
| Device length (mm) | 110 |
| Device width (mm) | 105 |
| Device height (mm) | 48 |
| Gefahrgut | No |