NOVOS 3 x
NOVOS 3 P white temp NTC10k, pot_active
Room operating unit temperature | Passive | Room Climate Control, Measure values
NTC10k
Application/type | Room operating unit |
---|---|
Purpose | Room Climate Control, Measure values |
Measured values | temperature |
Interface | Passive |
Functions | temperature control |
Operating functions | setpoint adjustment temperature |
Operating elements | potentiometer (P), active 0..10 V, labelling {- [scale] +} |
Configuration | jumper |
Sensor | NTC10k |
Operating range temperature (°C) | -35..+70 |
Operating ranges temperature (°C) | -35..+70 |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,2 K (typ. at 25 °C, temperature dependend) |
Enclosure | PC V0 |
Colour | pure white |
Protection (IP) | IP20, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) | 115 |
Packaging width (mm) | 105 |
Packaging height (mm) | 30 |
Packaging | case packaging |
Device length (mm) | 110 |
Device width (mm) | 100 |
Device height (mm) | 23 |
Option enclosure | ePaper Display 44x24 mm |