NOVOS 5
NOVOS 5 CO2+VOC temp white LCD RS485 BACnet (MS/TP)
Room sensor temperature, CO2, VOC, CO2/VOC mix | RS485 BACnet | 0..+50 °C
0..2000 ppm, 0..5000 ppm, optionally configurable
Application/type | Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, CO2, VOC, CO2/VOC mix |
Interface | RS485 BACnet |
Configuration | NOVOSapp, uConfig, BUS |
Input | 1x input for floating contact |
Network technology | RS485 BACnet (MS/TP) |
Operating range temperature (°C) | 0..+50 |
Operating ranges temperature (°C) | 0..+50 |
Operating range humidity | max. 85% rH non-condensing |
Measuring range CO2 | 0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) | heated metal oxide semiconductor |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Power consumption | typ. 0,4 W (24 V =), 0,8 VA (24 V ~) |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | PC V0 |
Colour | pure white |
Protection (IP) | IP30, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) | 170 |
Packaging width (mm) | 110 |
Packaging height (mm) | 45 |
Device length (mm) | 163 |
Device width (mm) | 106 |
Device height (mm) | 25 |
Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |