Application/type |
Cable sensor, Surface sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
Active, 0..5 V, 0..10 V |
Configuration |
jumper |
Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Output voltage |
0..10 V or 0..5 V, adjustable via jumper, min. load 5 kΩ |
Operating range temperature (°C) |
-35..+70 |
Operating ranges temperature (°C) |
-35..+70 |
Output signal temperature |
scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer |
Operating range temperature enclosure (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, depending on length of connection wire, potentiometer for offset adjustment |
Power supply |
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
typ. 0,4 W (24 V =), 0,8 VA (24 V ~) |
Material in touch with media |
Sensor probe, aluminium, 35x10x6 mm |
Installation length (mm) |
35 |
Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Connection cable |
PVC, 0,25 mm², 2-wire, white |
Length connection wire (m) |
1 |
Mounting |
surface mounting due to self-adhesive sensor surface |
Delivery content |
incl. mounting base enclosure USE-S pure white, incl. mounting set (screws and accessories) |
Packaging length (mm) |
170 |
Packaging width (mm) |
120 |
Device length (mm) |
63 |
Device width (mm) |
68 |
Device height (mm) |
40 |
Weight (g) |
115 |