WRF06
WRF06 CO2+VOC temp_rH 4xV TLF Jung LS 990 pure white brilliant/alpin white
Room sensor temperature, relative humidity, CO2, VOC, CO2/VOC mix | Active, 0..10 V | 0..+50 °C
0..100% rH non-condensing
0..2000 ppm NDIR (non-dispersive, infrared)
Application/type | Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, relative humidity, CO2, VOC, CO2/VOC mix |
Interface | Active, 0..10 V |
Sensor | NDIR (non-dispersive, infrared) |
Output voltage | 4x 0..10 V, min. load 10 kΩ |
Operating range temperature (°C) | 0..+50 |
Operating ranges temperature (°C) | 0..+50 |
Output signal temperature | scaling analogue output, 0..+50 °C |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Measuring range humidity | 0..100% rH non-condensing |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 | 0..2000 ppm |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) | heated metal oxide semiconductor, self-calibration |
Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | max. 1,6 W (24 V =), 3,9 VA (24 V ~) |
Enclosure | PC, central disc Thermokon (frame selectable) |
Colour | alpin white |
Protection (IP) | IP30, according to EN 60529 |
Connection | terminal block, max. 1,5 mm², pluggable, cable entry via rear opening |
Switch ranges | Jung |
Switch range Jung | LS 990 with intermediate frame |
Mounting | flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm) |
Delivery content | incl. frame |
Packaging length (mm) | 90 |
Packaging width (mm) | 90 |
Packaging height (mm) | 80 |
Packaging | case packaging |
Device length (mm) | 81 |
Device width (mm) | 81 |
Device height (mm) | 46 |
Gefahrgut | No |