MWF400+
MWF400+ TRV MultiRange
Duct averaging sensor -30..+80 °C | Active, 0..5 V, 0..10 V | IP65 according to EN 60529
Sensor rod, copper, bendable, Ø=4 mm, Sensor neck, stainless steel V4A (1.4571), Ø=6 mm, 400 mm
Application/type | Duct averaging sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | Active, 0..5 V, 0..10 V |
Configuration | jumper |
Output voltage | 0..10 V or 0..5 V, adjustable via jumper, min. load 5 kΩ |
Operating range temperature (°C) | -30..+80 |
Operating ranges temperature (°C) | -30..+80 |
Output signal temperature | scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer |
Operating range temperature enclosure (°C) | -35..+70 |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment |
Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | typ. 0,4 W (24 V =), 0,8 VA (24 V ~) |
Material in touch with media | Sensor rod, copper, bendable, Ø=4 mm, Sensor neck, stainless steel V4A (1.4571), Ø=6 mm |
Installation length (mm) | 400 |
Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Delivery content | incl. mounting clip enclosure USE-S pure white, incl. fixing kit rawlplugs and screws (2x each) |
Packaging length (mm) | 70 |
Packaging width (mm) | 70 |
Packaging height (mm) | 500 |
Packaging | case packaging |
Device length (mm) | 63 |
Device width (mm) | 68 |
Device height (mm) | 440 |