Application/type |
CO2 Traffic Light, Room sensor |
Purpose |
Measure values |
Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix, luminosity, motion, presence |
Interface |
Passive, Active, 0..5 V, 0..10 V, 4..20 mA, EnOcean (868 MHz), LoRaWAN® (868 MHz), RS485 Modbus, RS485 BACnet |
Configuration |
NOVOSapp, App, uConfig, BUS, jumper, DIP switches, ETS (KNX), LoRaWAN® Downlink, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig, (depending on type) |
Sensor |
NTC10k, Pt1000 DIN cl. B, Ni1000 DIN cl. B, Pt1000 1/3 DIN, Pt100 DIN cl. B, Ni1000TK5000, Pt100 1/3 DIN, passive, PIR (passive infrared), ambient light sensor with precise optical filtering appropriate to the human eye |
Output voltage |
0..10 V or 0..5 V, 2x 0..10 V or 0..5 V, 3x 0..10 V or 0..5 V, 4x 0..10 V or 0..5 V, live-zero configuration via app or uConfig, min. load 10 kΩ |
Output current |
4..20 mA, 2x 4..20 mA, max. load 500 Ω |
Input |
1x input for NTC10k or floating contact, 1x input for floating contact, 2x input for floating contact |
Network technology |
RS485 Modbus, RS485 BACnet (MS/TP), KNX (TP1) |
Radio technology |
EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW, EEP A5-02-05 (4BS), EEP A5-04-01 (4BS), LoRaWAN® (868 MHz) |
Data transmission |
bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit), wake up time: 100 sec. (default), or 240 sec. (adjustable by DIP switch), heartbeat cycle: every 10th wakeup, every 100 seconds if temperature change >0,3 K, humidity change >1,6% rH |
Operating range temperature (°C) |
-35..+70 |
Operating ranges temperature (°C) |
0..+40, 0..+50, -35..+70 |
Output signal temperature |
scaling according EEP, 0..+40 °C, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,4 K (typ. at 21 °C), ±0,5 K (typ. at 21 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend) |
Measuring range humidity |
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 |
0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) |
heated metal oxide semiconductor |
Measuring range light |
selectable from 6 ranges 0..200 lux | 0..1000 lux | 0..2 klux | 0..10 klux | 0..20 klux | 0..50 klux |
Accuracy light |
±5% of measuring range |
Dectection range |
detection range, angle 110°/110°, 32 detection zones – at a distance of 2,5 m the detection area will be about 5x5 m, max. range 5 m |
Power supply |
24 V = (±10%) SELV, 15..35 V = SELV, 19..29 V ~ SELV, solar cell, maintenance-free internal super cap, use of back-up battery possible for insufficiently lit environments, battery ER14505 (3,6 V), battery type AA (1x), mains adapter 100..230 V (50/60 Hz), max. 0,4A, Flush-mounted power supply 230 V (±10%, 50/60 Hz), max. 0.4 A, supply via BUS, 29 V = SELV |
Power consumption |
typ. 0,4 W (24 V =), max. 0,5 W (24 V =), 0,8 VA (24 V ~) |
Display |
ePaper Display 44x24 mm, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure |
PC V0 |
Colour |
pure white, black |
Protection (IP) |
IP20, according to EN 60529 |
Connection |
tool-free mountable spring clamp, max. 1,5 mm², removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Connection cable |
2-wire, 4-wire |
Mounting |
flush-mounted on standard EU box (Ø=60 mm), flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Delivery content |
incl. adhesive foil for mounting, incl. stand and power supply unit |
Packaging length (mm) |
115 |
Packaging width (mm) |
105 |
Packaging height (mm) |
30 |
Packaging |
case packaging |
Device length (mm) |
110 |
Device width (mm) |
100 |
Device height (mm) |
23 |
Notes |
mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...), Please note our sheet 'Information EasySens® Radio' |
Option enclosure |
ePaper Display 44x24 mm |
Gefahrgut |
No |